2 how to use para, 2 how to use, How to register functions to keys – Sonic Alert Digital Program Controller DCP301 User Manual

Page 89

Advertising
background image

Chapter 7. PARAMETER SETUP

7-4

7-2

How to Use

PARA

Use

PARA

for calling up individual items in frequently changed parameters.

How to register functions to keys

Up to eight individual items in the parameter setup can be assigned to each

PARA

key. The

assignment item must be registered to use this feature.

This feature allows you to call up individual items more easily in the following order:

FUNC

+

PARA

selection of setting group

individual item matrix.

How to register assignment items

To register an assignment item, add the following base corresponding to the setting group
to the item No., and then set the resultant value to setup data

C 5 5 to C 6 2 (

PARA

assign-

ment items 1 to 8)).

Base

Setting Group

1000

Constant-value operation data

1500

PID parameters

2500

Variable parameters

3500

Event configuration data

4000

Table data

4500

Setup data

Advertising