Chapter 4. WIRING

4-13

4-11 Connecting Time Event Output (open-collector)

Optional time event outputs T1 to T5 (open-collector outputs) can be added on. Time event outputs are connected on
the add-on terminal base.

56

53

55

51

52

49

50

10 to 29Vdc

T1

T2

T3

T4

T5

Load

Load

Load

Load

Load

External power supply

Add-on terminal base

Bias circuit

Maximum load current:
OFF leakage current:

70mA/load
0.1mA max.

• Be sure to connect terminal (55) to the + terminal of the external power supply.

Otherwise, open-collector output will not function.

• Do not short-circuit the + terminal of the external power supply and terminals

(49) to (53) on the DCP301. Doing so will cause faulty open-collector output.

(The DCP301 does not contain a short-circuit prevention circuit.)

• When connecting to a semiconductor load such as a programmable controller

(sequencer), select a module whose current directions are matching.

Use a module that does not operate by leakage current when the open-collec-
tor output of the DCP301 is OFF.

Handling Precautions