Chapter 4. WIRING

4-6

4-5

Connecting the Ground and Power Supply

Power supply

Connect the DCP301 to a single-phase power supply for controllers, and take measures
to prevent the influence of electrical noise.

1

3

2

1

2

E

3

4

GND

~

Instrument
power supply

Other circuits

GND

GND

Recommended

line filter

81446364-001

DCP301

200/200V,

100/100V

insulated transformer

• If the power supply generates a lot of electrical noise, we recommend inserting

an insulating transformer in the power circuit and using a line filter.

Recommended line filter: Model No. 81446364-001

• After providing anti-noise measures, do not bundle primary and secondary power

leads together, or pass them through the same piping or wiring duct.

Ground

When it is difficult to ground shielded cable, prepare a separate ground terminal (earth
bar).

Ground type: 100

max.

Ground cable: 2mm sq. min soft-copper wire (AWG14)
Cable length: Max. 20m

3

FG
terminal

DCP301

GND terminal plate

GND (100

max.)

Shielded cable

Use only the FG terminal (3) on the DCP301 for grounding. Do not ground across
other terminals.

Handling Precautions

Handling Precautions