Chapter 4. WIRING

4-16

4-13 Connecting for Communications

Some controller models support the RS-485 communications interface. Select the RS-485 communications models
by selected the required catalog No.

Connect as follows.

The DCP301 operates as a slave station.

RS-485 interface

57

58

59

60

61

SDA

SDB

RDA

RDB

SG

Add-on terminal base

• Multi-drop connection of slave stations is possible.

• Make sure that different addresses are set for each slave station.

• Provide terminating resistor (total of 4 in the case of a 5-wire system connec-

tion) on both ends of the communications path. Use terminating resistor of
150

Ω±

5%, 1/2W min.

• In the case of a 3-wire system connection, short-circuit terminals (57) and (59),

(58) and (60) on the DCP301.

• Do not short-circuit the RDA and RDB, or SDA and SDB terminals. Doing so

might damage the DCP301.

Handling Precautions

Handling Precautions