Square root computation – Omega RD100B User Manual

Page 101

Advertising
background image

5-7

Frequently Used Setup Operations (Setting Mode)

5

Square Root Computation

Select SQRT.

Set the channel range.

Select the range type of DC voltage.
20 mV, 60 mV, 200 mV, 2 V, 6 V, 20 V,
or 50 V

Set the left span value.

Set the right span value.

Set the left scale value.

Set the right scale value.

Turn On or Off the low-cut function.

Set the low-cut point.

0.0 to 5.0% of the recording span, 0.1 steps.

The new setting takes effect.

First channel Last channel

ESC/?

Set=Range

CH=01-01

Mode=SQRT

Range=2V

Span_L= -2.000

Span_R= 2.000

Scale_L= 0.00

Scale_R= 200.00

Low-cut=Off

Low-cut point=0.0

01-01 Channel
Setting complete

Description

• Input Type in Which Square Root Computation Can Be Performed

Square root computation can be performed when set to DC voltage input.

• Span Left and Span Right

Same as the selectable span range of the DC voltage input.

Make sure that span left is less than span right.

• Scale Left and Scale Right

Selectable range (mantissa): –20000 to 30000

Decimal position: XXXXX, XXXX.X, XXX.XX, XX.XXX, X.XXXX

The decimal position is the position specified by scale left.

Make sure that scale left is less than scale right.

• Low-cut and Low-cut Point

If low-cut is set to On, set the low-cut point.

Selectable range of the low-cut point: 0.0 to 5.0% of the recording span

Values below the low-cut point is set to 0% (scale left value) of the recording span.

5.1 Setting the Input range