2-11

Before Using the Recorder

2

Wiring Procedure

1.

Turn OFF the recorder and remove the terminal cover.

2.

Connect the input signal wires to the terminals.

Philips
screwdriver

Crimp-on lug with
insulation sleeves

3.

Replace the terminal cover and fasten it with screws.

The proper torque for tightening the screws is 0.6 N-m.

Transistor input
(Open collector)

Relay contact input
(Voltage-free contact)

1

2

3

4

5

C

1

2

3

4

5

C

Relay contact output

C

NO

NC

Alarm output
FAIL/chart end output

Remote control input

Note

To reduce noise, use a shielded cable for the wiring of the remote control input terminals.

Connect the shield to the ground terminal of the recorder.

• Relay Contact Output Specifications

Output type:

Relay

Contact rating:

250 VAC (50/60 Hz)/3 A, 250 VDC/0.1 A (resistive load)

Dielectric strength:

1500 VAC at 50/60 Hz for one minute (between output

terminals and the ground terminal)

• Relay Contact Input/Transistor Input Specifications

Input signal:

• Voltage-free contact: Contact closed at 200 Ω or less and

contact open at 100 kΩ or greater

• Open collector: 0.5 V or less (30 mADC) when turned ON,

leakage current of 0.25 mA or less when turned OFF

Input format:

Photocoupler isolation (shared common)

Dielectric strength:

500 VDC for one minute between input terminals and the

ground terminal