1-7

Functional Description

1

1.3

Alarms

This function generates an alarm when the measured data meets a certain condition.

The alarm occurrence/release can be recorded on the chart paper. The alarm status can

be displayed on the screen.

Also, alarm output relays can be used to output contact signals when alarms occur (/A1,

/A2, and /A3 options).

Alarm Types

Number of Alarm Point Marks

Up to four alarms can be set for each channel.

Alarm Conditions

The eight conditions below are available. The character inside the parentheses is the

symbol used to denote each alarm on the recorder.

• High Limit Alarm (H)

An alarm occurs when the input value exceeds the alarm value.

• Low Limit Alarm (L)

An alarm occurs when the input value falls below the alarm value.

Alarm
value

Alarm release

Measured value

Alarm occurrence

High limit alarm

Low limit alarm

Measured
value

Alarm release

Alarm value

Alarm occurrence

• Difference High Limit Alarm (h)*

An alarm occurs when the difference in the input values of two channels is greater

than or equal to the specified value.

• Difference Low Limit Alarm (l)*

An alarm occurs when the difference in the input values of two channels is less than

or equal to the specified value.

*

Can be specified on channels set to delta computation.

• High Limit on Rate-of-Change Alarm (R)

The rate-of-change of the measured values is checked over a certain time (interval).

An alarm occurs if the rate-of-change of the measured value in the rising direction is

greater than or equal to the specified value.

• Low Limit on Rate-of-Change Alarm (r)

The rate-of-change of the measured values is checked over a certain time (interval).

An alarm occurs if the rate-of-change of the measured value in the falling direction is

greater than or equal to the specified value.

Measured
value

Change in the
measured value

T1

Time

Interval

T2

t1

t2

Amount of change
in the setting

T2

Time

T1

t1

t2

Measured
value

Change in the
measured value

Amount of change
in the setting

|

|

High limit on rate-of-change alarm

Low limit on rate-of-change alarm

t2t1

Interval

t2t1

T2T1

|

|

T2T1

The alarm value of the rate-of-change alarm is set using an absolute value. The

interval is derived using the following equation and set using the number of samples.

Interval = the scan interval × the number of samples