1 changing the auxiliary alarm function – Omega RD100B User Manual

Page 124

Advertising
background image

7-1

Setup Operations for Changing/Adding Functions (Basic Setting Mode)

7

7.1

Changing the Auxiliary Alarm Function

This section explains the details of setting the alarm system items listed below.

• Diagnosis output using the alarm output relay (I01)

• Reflash alarm operation of the alarm output relay (I01 to I03)

• AND/OR operation of alarm output relays

• Energized/De-energized operation of alarm output relays when alarms occur

• Hold/Non-hold operation of alarm output relays

• Hold/Non-hold operation of alarm indications

• The interval of the rate-of-change alarm

• Alarm hysteresis

Basic Setting mode cannot be entered when recording is in progress or when

computation is in progress on models with the computation function (/M1 option).

Procedure

Changing the Settings

1.

Hold down the

MENU

key for 3 seconds to enter Setting mode.

2.

Hold down the

and

keys simultaneously for 3 seconds to enter Basic

Setting mode.

3.

Press the

key with Alarm shown on the screen.

4.

Set each item and press the

key.

Use the

key or SHIFT +

key to select values.

For the procedure on how to enter values or characters, see section 4.2.

If you press the ESC key in the middle of the operation, the settings entered up

to then are cancelled, and the display returns to a higher level menu.

5.

When the Setting complete screen appears, do either of the following:

To correct the setting, press the

key.

If you are done, press the ESC key.

Chapter 7 Setup Operations for Changing/Adding Functions (Basic Setting Mode)