1-12

Non-Hold/Hold Operation of Alarm Output Relays

The alarm output relay can be set to operate in the following fashion when the alarm

condition is no longer met.

• Turn off the relay output (non-hold).

• Hold the relay output until the alarm ACK operation is executed (hold).

The setting applies to all alarm output relays.

The default setting is non-hold.

Alarm

Alarm occurrence

Alarm release

Alarm output
relay

Alarm
ACK

Alarm
ACK

Alarm
ACK

or

or

Hold

Non-hold

Activated

Released

Note

If the reflash alarm is enabled, I01 to I03 are fixed to non-hold operation. Specifying Hold

produces no effect.

If diagnosis output is enabled, I01 is fixed to non-hold operation. Specifying Hold produces

no effect.

<Related Topics>

Setting the non-hold/hold operation of alarm output relays: Section 7.1

Alarm ACK Operation

The alarm acknowledge (alarm ACK) operation releases all alarm indications and relay

outputs (/A1, /A2, and /A3 options) that are activated when the alarm indication or alarm

output relay is set to hold operation. This operation can be executed from the front panel

key.

<Related Topics>

Alarm ACK operation: Section 3.12