2.5

Power Supply Wiring

Precautions to Be Taken While Wiring the Power Supply

Make sure to follow the warnings below when wiring the power supply. To prevent

electric shock and damage to the recorder, observe the following warnings.

WARNING

• To prevent electric shock when wiring, ensure the main power supply is turned

OFF.

• To prevent the possibility of fire, use 600 V PVC insulated wire (JISC3307) or an

equivalent wire for power wiring.

• Make sure to earth ground the protective earth terminal through a grounding

resistance less than 100 Ω before turning ON the power.

• Use crimp-on lugs (designed for 4 mm screws) for power and ground wiring

termination.

• To prevent electric shock, make sure to close the transparent cover for the

power supply wires.

• Make sure to provide a power switch (double-pole type) on the power supply

line in order to separate the recorder from the main power supply. Put an

indication on this switch as the breaker on the power supply line for the recorder

and indications of ON and OFF.

Switch specifications

Rated power current: 1 A or more

Rated rush current: 60 A or more

Use a switch complied with IEC 60947-1, 3.

• Connect a fuse between 2 A and 15 A in the power supply line. Use a fuse

approved by CSA (for the use in North America) or VDE (for the use in Europe).

• Do not add a switch or fuse to the ground line.

Use a power supply that meets the following conditions:

Item

Power Supply Specifications

Rated supply voltage

100 to 240 VAC

Allowable power supply voltage range

90 to 132/180 to 264 VAC

Rated supply voltage frequency

50/60 Hz

Allowable power supply frequency range

50/60 Hz±2%

Maximum power consumption

Pen model: 40 VA, dot model: 40 VA

Note

Do not use a supply voltage in the range 132 to 180 VAC, as this may have adverse effects

on the measurement accuracy.

Advertising