Measuring input wiring – Omega RD100B User Manual

Page 52

Advertising
background image

2-8

Measuring Input Wiring

DC voltage

1-5V

ON/OFF

Extension leadwire

DC current

Shunt resistor

–/B

b

+/A

–/B

b

+/A

–/B

b

+/A

–/B

b

+/A

+

+

Thermocouple input

Resistance temperature detector input

DC voltage input, 1-5V input,
and ON/OFF input

DC current input

Leadwire resistance:
10

max./wire. The resistance

of the three wires should be
equal.

Example: For a 4 to 20 mA
input, a shunt resistor of
250

± 0.1% can be used to

convert to 1-5V input.

A

B

b

Note

RTD input terminals A and B on the dot model are isolated on each channel. Terminal b is

shorted internally across all channels. However, for 3 legs isolated RTDs (/N2 option), input b

is also isolated for each channel.

2.3 Input Signal Wiring