Explanation

Channel Range

The only case when an alarm can be set on multiple channels simultaneously is when

the channels are set to the same range type (for example channel 01 and 02 are set to 2

V range). For channels on which scaling is set, the channels must be set to the same

range type, same span values, and same scaling values.

Alarm Type

Symbol

Name

Note

H

High limit alarm

L

Low limit alarm

h

Difference high limit alarm

Can be specified on channels set to
delta computation.

l

Difference low limit alarm

Can be specified on channels set to
delta computation.

R

High limit on rate-of-change alarm

r

Low limit on rate-of-change alarm

T

Delay high limit alarm*

t

Delay low limit alarm*

*

Selectable only when the alarm delay function is enabled. See section 7.15.

Note

On channels set to delta computation, alarms can be detected on the values illustrated in the

figure below.

Input value

Measured value on the reference channel

Alarm on a channel set to delta computation

Alarm
H, L, R, r, T, and t

Alarm
h and l

Measured value

If high limit on rate-of-change alarm or low limit on rate-of-change alarm is specified, set

the interval over which the rate-of-change is calculated.

If delay high limit alarm or delay low limit alarm is specified, set the delay time.

<Related Topics>

Setting the interval of the high limit on rate-of-change alarm or low limit on rate-of-

change alarm: Section 7.1

Setting the delay time of delay high limit alarm or delay low limit alarm: Section 6.10

Enabling the alarm delay function: Section 7.15

Setting the alarm hysteresis: Section 7.1

Alarm Value

• High Limit Alarm/Low Limit Alarm and Delay High Limit Alarm/Delay Low Limit

Alarm

The following values can be specified.

• For DC voltage, TC, and RTD input: Values within the measurable range in the

specified range (example: –2.000 to 2.000 V for the 2 V range).

• For ON/OFF input (DI): 0 or 1.

• For linear scaling (1-5V, scaling, and square root): A value within –5 to 105% of the

scaling span except within the range of –20000 to 30000 (excluding the decimal

point).

5.2 Setting the Alarm