Fail output, Chart end output – Omega RD100B User Manual

Page 41

Advertising
background image

1-27

Functional Description

1

1.7

FAIL/Chart End Detection and Output Function
(/F1 Option)

FAIL Output

When a failure occurs in the CPU of the recorder, a relay contact signal (1 signal) is

output. The relay is energized when the CPU is normal and de-energizes when a CPU

failure occurs. Therefore, relay output is carried out also when the power is turned OFF

(including a power failure). This relay behavior cannot be changed.

• FAIL Relay Output

NO

C

NC

Normal

NO

C

NC

Failure

NO

C

NC

Power-OFF

NO: Normally Opened, C: Common, NC: Normally Closed

Chart End Output

When the remaining amount of chart paper falls to approximately 2 cm, recording is

stopped, and the relay contact signal (1 relay) is output. The relay is energized in this

case. This relay behavior cannot be changed.

NO

C

NC

Normal

NO

C

NC

Chart end

NO

C

NC

Power-OFF

NO: Normally Opened, C: Common, NC: Normally Closed