4-3 terminating resistance, Terminating resistance – Omron CQM1H-CLK21 User Manual

Page 105

Advertising
background image

82

Constructing Networks with Repeater Units

Section 3-4

The path from one node to another travels via three Repeater Units
(3 stages). This kind of network is NOT allowed.

Note If the Repeater Units are used incorrectly, communications errors may occur,

or nodes may not be able to participate in the network.

3-4-3

Terminating Resistance

In a Wired Controller Link Network, turn ON the terminating resistance
switches only at the nodes at both ends of the network.

When Repeater Units are used to divide the network into multiple segments,
turn ON the terminating resistance switches of the nodes at both ends of each
segment. When a Repeater Unit is connected to the end of a segment, turn
ON the built-in terminating resistance switch of the Repeater Unit itself.

Connection examples are shown below.

T-Branch Wiring

Long-distance Wiring

Terminating
resistance: ON

Terminating
resistance: ON

Terminating
resistance: ON

Terminating
resistance: ON

Terminating
resistance: ON

Terminating
resistance: ON

Segment 1

Segment 2

Segment 3

CS1W-RPT01
Repeater Unit

Terminating resistance is turned ON at both ends of
each segment. (Repeater Units are also equipped
with a built-in terminating resistance switch.)

Terminating
resistance: ON

Terminating
resistance: ON

Terminating
resistance: ON

Terminating
resistance: ON

Terminating
resistance: ON

Terminating
resistance: ON

Segment 1

Segment 2

Segment 3

CS1W-RPT01
Repeater Unit