Handling Precautions

Section 9-6

CVM1 and CV-series Controller Link Units

CQM1H-series Controller Link Units

2.

Turn the power off once, connect the Controller Link Network and turn the
power on again. Check that the Unit is participating in the Network.

If the INS indicator is lit and the ERC and ERH indicators are off, then the
Unit is in the Network.

3.

Return the Polled node/polling node setting of the node in which the Unit
was replaced to “polling node.” For C200HX/HG/HE and CQM1H-series
Controller Link Units, the EEPROM Clear bit will already be set to not clear
EEPROM.

CS/CJ-series Controller Link Units

C200HX/HG/HE Controller Link Units

CVM1 and CV-series Controller Link Units

CQM1H-series Controller Link Units

4.

Restart the Controller Link Unit or turn the power off and then back on
again, and then check to see if the Unit is participating in the Network.

If the INS indicator is lit and the ERC and ERH indicators are not lit, then
the Unit is in the Network.

Note Restart the Unit only when the data links are halted.

0: Polling node mode
1: Polled node

Polled node/polling node

– : Other settings

DM 2000 + 100

×

n

n = Unit number

DM 6400

–: Other settings

EEPROM Clear Bit

0: Do not clear EEPROM
1: Clear EEPROM

Polled node/polling node 0: Polling node

1: Polled node

0: Polling node
1: Polled node

Polled node/Polling node

– : Other settings

DM 30000 + 100

×

n

n = Unit number

Operating level 0
DM 6400

Operating level 1
DM 6420

–: Other settings

EEPROM Clear Bit

0: Do not clear EEPROM
1: Clear EEPROM

Polled node/polling node 0: Polling node

1: Polled node

0: Polling node mode
1: Polled node

Polled node/Polling node

– : Other settings

DM 2000 + 100

×

n

n = Unit number

DM 6400

–: Other settings

EEPROM Clear Bit

0: Do not clear EEPROM
1: Clear EEPROM

Polled node/polling node 0: Polling node

1: Polled node