Omron CQM1H-CLK21 User Manual

Page 96

Advertising
background image

73

Wiring

Section 3-3

5.

Move the cable connector so that the loose ends are on the left-hand side,
and insert the Unit’s optical connector as far as it will reach.

• Insert the connectors completely and always check that the connectors

are locked before starting operation.

Even in token-ring mode, the network will be broken and communications may
be disrupted if disconnections occur at two or more places. Be sure not to
allow connectors to be disconnected during communications.

• Do not pull on the Optical Fiber Cable too forcefully.

The maximum tension that can be applied to the cord is 10 kg and the
maximum tension that can be applied to the cable is 50 kg.

• Do not bend the cable too sharply. The minimum radius for bends is

10 cm.

• To prevent the Optical Fiber Cable from being pulled too forcefully, always

use the cable securing bracket and provide space below the Unit as
shown in the following diagram. Do not exceed the maximum tension for
the cord and cable:

Cord:

0 kg (Do not apply any tension.)

Cable: 5 kg

• Do not place objects on top of the Optical Fiber Cable. The maximum

pressure that can be placed on the cord and cable is as follows:

Cord:

30 kg/10 cm

Cable: 50 kg/10 cm

• Inspect the connector before installing it.

DC24V

INPUT

SL1

SL2

T/R2

T/R1

PWR

CS1W-RPT02

BD L

SHLD

BD H

TER SW

ON

ON

SW1

BAUD
RATE

1
2

+

Example: Connections for Duplex Operation of Communications Units

Mounting bracket

Tension member

Terminal

Cord

Cable

Cord

Cable

Advertising
This manual is related to the following products: