150

Setting Data Links

Section 5-2

CQM1H-series Startup Node

Set the following DM Parameter Area of the PLC of the startup node.

Settings

Data link mode
Set to 01 for automatic setting.
(00 is for manual setting. Other values are invalid.)

Number of send words per node of area 1 (BCD)

Rightmost 4 digits of data link start word of area 2 (BCD)

Leftmost digit of data link start word
of area 2 (BCD)

First data link status word (BCD)

DM 6400

0: Always 0.
– : Other settings

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

15

8

7

0

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

DM 6401

DM 6402

DM 6403

DM 6404

DM 6405

DM 6406

DM 6408

32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17

DM 6409

0

0

0

0

0

0

0

0

0

0

0

DM 6407

00

Area 2 type

Number of send words per node of area 2 (BCD)

Area 1 data link start word (BCD)

Area 1 type

BCD: Set the value as binary-coded decimal.

Nodes to participate in the data links

The numbers indicate node numbers.
The value assigned indicates whether the
node is to participate in the data links.

Participate: 1
Not participate: 0

Item

Setting range

Data link mode

Specify automatic (01).

Area 1 data link start
word

Set the word address in BCD.

IR Area: IR 0000 to IR 247

LR Area: LR 00 to LR 63

Area 1 type

Set the area for area 1 in BCD.

IR Area:

80

LR Area:

86

Area 1 not used: 00

Send size (number of
words) for node of area 1

Set the number of words in BCD between 0 and 1,000.

The total number of send words of area 1 and area 2
must not exceed 1,000.

When area 1 is not used, set to 0.

Area 2 data link start
word

Set the word address in BCD.

DM Area: DM 0000 to DM 5999

EM Area:

EM 0000 to EM 6143 (EM must be installed)

Area 2 type

Set the area for area 2 in BCD.

DM Area:

82

EM Area: 90

Area 2 not used: 00

Send size (number of
words) for node of area 2

Set the number of words in BCD between 0 and 1,000.

The total number of send words of area 1 and area 2
must not exceed 1,000.

When area 2 is not used, set to 0.