152

Setting Data Links

Section 5-2

Data Link Areas Created

DM Parameter Setting
Example for 1:N
Allocation, Common Type

When automatic data link creation with common type1:N allocations is used,
the DM Parameter Area of the startup node is set as follows:

*: The default area for storing data link status is the Special I/O Unit Area

(CIO 1500 + (25

×

Controller Link Unit number) +7 to +22).

#3

Area 1

Area 2

Node #1

Node #2

Node #3

LR 0

LR 10

LR 20

D1000

D1200

D1400

#1

#1

#1

#2

#3

#1

#2

#3

#2

#1

#2

#3

#2

#3

#1

#2

#3

N

0050

N+1 to N+11

0000

N+12

0001

N+13

0100

N+14

80

00

N+15

0030

N+16

0020

N+17

1000

N+18

82

00

N+19

0400

N+20

0200

N+21

0000

N+22

000F

N+23

0000

N+24

0000

N+25

0000

Word

Setting

Data link mode: Automatic 1:N allocation

"0" because equality layout allocations are not used.

Common type

Area for area 1: CIO Area

Start word: 100

Area 1 send size for master node: 30

Area 1 send size for slave nodes: 20

Area for area 2: DM Area

Start word: D1000

Area 2 send size for master node: 400 words

Area 2 send size for slave nodes: 200 words

Data link status stored in default area (*)

Data link participating nodes: #1, #2, #3, and #4