228

Response Codes

Section 6-7

01: Local node error

01

Local node not part of Network

Add to Network.

02

Token time-out, node address too large Set the local node’s node address below

the maximum node address.

03

Number of transmit retries exceeded

Check communications with ECHOBACK
TEST. If the test fails, check network.

04

Maximum number of frames exceeded

Either check the execution of events in the
network and reduce the number of events
occurring in one cycle, or increase the max-
imum number of frames.

05

Node address setting error (range)

Correctly set the Controller Link BIOS /N
option. Make sure the node address is
within specified range and that there are no
node addresses that are set twice.

06

Node address duplication error

Make sure that there are no node
addresses that are set twice.

02: Destination node
error

01

Destination node not part of Network

Add to Network.

02

No node with the specified node
address

Check the destination node’s node address.

03

Third node not part of Network

Check the third node’s node address.

Broadcasting was specified.

Check the control data and specify only one
node as the third node.

04

Busy error, destination node busy

Increase the number of transmit retry
attempts or re-evaluate the system so that
the destination node is not so busy receiv-
ing data.

05

Response time-out, message packet
was corrupted by noise

Increase the number of transmit retry
attempts.

Response time-out, response watch-
dog timer interval too short

Increase the value for the response watch-
dog timer interval in the control data.

Frame lost in transmission

Check the error log and correct the process.

03: Communications con-
troller error

01

Error occurred in the communications
controller, ERC indicator is lit

Take corrective action, referring to commu-
nications controller errors and remedies
table at end of this section.

02

CPU Unit error occurred in the PLC at
the destination node

Clear the error in the CPU Unit (refer to the
PLC’s operation manuals).

03

A controller error has prevented a nor-
mal response from being returned.

Check network communications status and
reset the controller board. If the error still
exists, replace the controller board.

04

Unit address setting error

Make sure the Unit address is within the
specified range and that there are no node
addresses that are set twice.

04: Not executable

01

An undefined command has been
used.

Check the command code and be sure that
the Unit supports it.

02

Cannot process command because the
specified unit model or version is
wrong.

Check the unit model and version.

Main code

Sub-

code

Probable cause

Remedy