Omron CQM1H-CLK21 User Manual

Page 221

Advertising
background image

198

Using the Message Service

Section 6-3

CVM1 and CV-series PLCs

Note When using the sample program, make sure that the bits and words used in

the sample program are not the same as those in the user program or Special
I/O Units.

(011)

I0000

00

A502

07

1200

02H

1200

01H

1210

00H

(030)

(030)

(030)

(030)

(030)

(040)

(192)

(013)

1200

00

A502

15

(011)
KEEP 120002H

I0000

01

A502

07

1200

00H

1200

03H

(030)

1200

02H

(030)

(030)

(030)

(030)

(193)

A502

07

1200

00

(013)

1210

01H

1200

02H

A502

07

1200

02H

A502

15

(040)

KEEP 120000H

MOV #000A

D00000

MOV #0002

D00001

MOV

#0400 D00002

MOV #0705

D00003

MOV #0064

D00004

XFER

#0010

I0000 D00010

SEND D00010

D00020 D00000

DIFU 120001H

MOV #0010

D00005

MOV #0003

D00006

MOV #2000

D00007

MOV #0705

D00008

MOV #0000

D00009

RECV A100

2000

D00005

DIFU 120003H

XFER

#0016

2000

D00040

1200

02H

03H

1200

A502

15

1200

00H

The transmission program will run when I000000 is ON,
provided that the Network Instruction Enabled Flag for
port 7 is ON and the RECV instruction has not been
executed.

CIO 120000H remains ON while the SEND instruction
is being executed, and it turns OFF when the execution
of the instruction has been completed.

Word

Content

Meaning

D00000 00

0A

No. of send words: 10H

D00002 04

00

Destination node address: 4

Destination unit address: 0

D00003 07

05

Response required

Communications port no.: 7

Number of retries: 5

The 10-word data starting from I0000 is stored in
D00010 and following words.

Transmission error display

The reception program will run when I000001 is ON,
provided that the Network Instruction Enabled Flag for
port 7 is ON and the SEND instruction has not been
executed.

CIO 120002H remains ON while the RECV instruction
is being executed, and it turns OFF when the execution
of the instruction has been completed.

Word

Content

Meaning

D00005 00 10

Number of receive words: 16H

D00006 00 03

Destination network address: 3

D00007 20 00

Destination node address: 32

Destination Unit address: 0

D00008 07 05 Response

required

Communications port no.: 7

Number of retries: 5

D00009 00 00

Response monitor time: Default

Reception error display
Reception data processing
When the data is received without an error, the 16-word
data received at CIO 2000 and following words is
stored in D00040 and following words on the same PLC.

Transfers 10 words of data from the source node (D00010)
to the PLC (from D00020 onwards) at network address 2,
node no. 4, unit address 0.

Creates reset input.

Transfers 16 words of data (from A100 onwards) from
the PLC at network address 3, node no. 32, unit address
0, to words 2000 onwards.

Creates reset input.

D00001 00 02 Destination network address: 2

D00004 00

64

Response monitor time: 10 s