2-1 message service operations, Message service operations – Omron CQM1H-CLK21 User Manual

Page 210

Advertising
background image

187

Selecting Communications Instructions

Section 6-2

6-2-1

Message Service Operations

Note

1.

CMND cannot be used with C200HX/HG/HE PLCs.

2.

If a computer is receiving commands, a program is required at the comput-
er for sending back responses.

Instruc-

tion

Source node

Destination node

Communica-

tions con-

tents

Data

length

Broad-

casting

Network con-

nections

C200HX/

HG/HE

CQM1H CS/CJ,

CVM1,

or CV

C200HX

/HG/HE

or

CQM1H

CS/CJ,

CVM1,

or CV

Com-
puter

SEND
and
RECV

Yes

Yes

Yes

Yes

Yes

Yes
(See
note
2.)

Read to and
write from all
I/O memory
areas.

990
words
max.
(1,980
bytes)

SEND
only (no
response)

Yes (up to
three levels
including local
network), via
CS/CJ-series,
CVM1, or
CV-series
PLCs.

CMND
(See
note 1.)

No

Yes

Yes

Yes

Yes

Yes
(See
note
2.)

Data
read/write:

Read to and
write from all
I/O memory
areas.

Read PLC
model.

Read status
data.

Read time
data.

Read and
write File
Memory data.

Read PLC
mode.

PLC Control:

Change PLC
mode.

Forced set/
reset

Clear PLC
errors.

2,012
bytes
max.

Yes (no
response)

Advertising
This manual is related to the following products: