273

Message Delay Times

Section 8-4

Note This communications cycle time is calculated assuming that there is no node

that transmits event frames before the SEND command is executed.

Link Unit servicing (source node)

×

2

PLC cycle time (source node)

×

2

Transmission processing (command)

3 ms

Communications cycle time

×

2 (See note.)

(600

Ч

4 + 110

Ч

32 + 320

Ч

0 + 4

Ч

0 + 2,290)

Ч

2 = 8,210

µ

s

×

2

16.4 ms

Transmission delay (command)

0.112

0.1 ms

Reception processing (command)

2.3 ms

Link Unit servicing (destination node)

PLC cycle time (destination node)

Transmission processing (response)

0.00125

×

256 + 3 = 3.32

3.3

Transmission delay (response)

0.008

×

256 + 0.112 = 2.16

2.2

Reception processing (response)

0.00125

×

256 + 2.3 = 2.62

2.6

Total (max. transmission delay)

PLC cycle time (source node)

×

2 + PLC cycle time (destination
node) + Peripheral servicing
time (destination node) +
29.9 ms