Data Links Procedures

Section 2-1

Chain Type

Note For automatic data link creation with 1:N allocations, use the CX-Net

in CX-Programmer version 3.2 or higher.

8.

Start the data links.

Note Data link Start/Stop Bit (N= unit number):

CS/CJ Series:

Word 0 of DM30000 + 100

×

N

C200HX/HG/HE:

AR 0700 (operating level #0),
AR 0704 (operating level #1)

CVM1/CV Series: Word 0 of DM 2000 + 100

×

N

CQM1H Series:

AR 0700

9.

Stop the data links.

Note Data link Start/Stop Bit (N= unit number):

CS/CJ Series:

Word 0 of DM30000 + 100

×

N

Contents

Method

Nodes

Page

a. Set the data link mode

to automatic.

Use Support Soft-
ware for the PLC
including Program-
ming Console (see
note).

Data link startup node
only

The node that is used
to start the data link is
called the startup
node. It is necessary
to decide beforehand
which node will be
the startup node.

113

b. 1:N creation

Data link startup node
only

141

c. Set the area

d. Set the data link start

word

e. Set the number of

common send words
per master node

f.

Set the number of
send and receive
words per node

g. Set the first data link

status word

h. Set the nodes to par-

ticipate in the data
links.

Contents

Method

Nodes

Page

Start the data links.

Switch the Data link
Start/Stop Bit (listed
below) from OFF to
ON using either the
Programming Device,
or the user program.

Data link startup node

(The Start Bit can be
turned ON in more
then one node to
make sure the data
links start even when
the startup node is
down.)

153

Contents

Method

Nodes

Page

Stop the data links.

Switch the Data link
Start/Stop Bit (listed
below) from OFF to
ON using either the
Programming Device,
or the user program.

Any node that is active
in the data link

153