Bit status and error processing – Omron CQM1H-CLK21 User Manual

Page 318

Advertising
background image

295

Status Area and Troubleshooting

Section 9-2

4-Bit Format Specified

The data link status can be reflected in 4-bit format only when using a CS1W-
CLK21-V1 or CJ1W-CLK21-V1. It is reflected in 8-bit format with other mod-
els.

When the first data link status word is set to the default (0000) for either the
manually set data link tables or automatically set data link tables (In the first
data link status word parameter), the data link status is stored in the above
area (CIO 1500 + 25

×

(Unit No.) (+ 7 to +22)).

When a different area has been set for the first data link status word, the sta-
tus is stored in the specified area. The status storage format is the same as
the one shown in the above diagram.

Note Refer to 5-4 Checking Data Link Status for details on status flags.

Bit Status and Error Processing

Data Link Status

Node 4

PLC status
0: Inactive (user program not running)
1: Active (user program running)

Communications error (data link reception)
0: Normal
1: Error

PLC's CPU Unit error
0: Normal
1: Error

Data link participation
0: Not in data link or data link inactive
1: In data link

Node 8

Node 12

Node 16

Node 20

Node 24

Node 30

Node 32

Node 36

Node 40

Node 44

Node 48

Node 52

Node 58

Node 60

0

Node 3

Node 7

Node 11

Node 15

Node 19

Node 23

Node 27

Node 31

Node 35

Node 39

Node 43

Node 47

Node 51

Node 55

Node 59

0

Node 2

Node 6

Node 10

Node 14

Node 18

Node 22

Node 26

Node 30

Node 34

Node 38

Node 42

Node 46

Node 50

Node 54

Node 58

Node 62

Node 1

Node 5

Node 9

Node 13

Node 17

Node 21

Node 25

Node 29

Node 33

Node 37

Node 41

Node 45

Node 49

Node 53

Node 57

Node 61

Bit status

Probable cause

Probable remedy

PLC’s CPU Unit error is 1:
ON

A fatal PLC error, non-fatal
PLC error, or a watchdog
timer error has occurred.

Refer to the PLC’s opera-
tion manual and correct
the error. If the error occurs
again, replace the PLC.

The Unit is mounted to a
non-compatible PLC.

Refer to 1-2-4 Controller
Link Unit Models and PLCs

and mount onto the correct
PLC.