What is Network Interconnection?

Section 7-1

7-1

What is Network Interconnection?

Network interconnection enables commands and responses for the message
service to be sent and received across multiple networks. The four networks
listed below can be interconnected to achieve this.

FA Networks

• SYSMAC NET Link Networks

• SYSMAC LINK Networks

• Controller Link Networks

OA Network

• Ethernet Networks

7-1-1

Interconnecting Controller Link Networks

Controller Link Networks can be connected through a CS/CJ-series, CVM1,
or CV-series PLC.

7-1-2

Interconnecting Different Types of Networks

A CS/CJ-series, CVM1, or CV-series PLC can be used to connect a Controller
Link Network with an Ethernet, SYSMAC NET, or SYSMAC LINK Network.

Note

1.

A bridge is used between Communications Units to connect the same type
of networks.

2.

A gateway is used between Communications Units to connect different
types of networks.

Controller Link Network

CS/CJ-series,
C200HX/HG/HE, CVM1,
CV-series, or CQM1H PLC

Note A data bridge is created between Controller Link Units mounted

on the same CS/CJ-series, CVM1, or CV-series PLC.

Controller Link Network

CS/CJ-series, CVM1, or
CV-series PLC (see note)

Note A data and communications protocol gateway is created between

a Controller Link Unit and an Ethernet, SYSMAC NET, or SYSMAC
LINK Unit mounted to the same CS/CJ-series, CVM1, or CV-series PLC.

Controller Link Network

Ethernet Network

CS/CJ-series,
C200HX/HG/HE, CVM1,
CV-series, or CQM1H PLC

CS/CJ-series, CVM1, or
CV-series PLC (see note)

Advertising