Omron CQM1H-CLK21 User Manual

Page 172

Advertising
background image

149

Setting Data Links

Section 5-2

2.

If the LR Area in a C200HX/HG/HE or CQM1H-series PLC is manually set
for a data link with a CVM1, CV-series, or CS/CJ-series PLC, the LR words
will be linked to CIO 1000 to CIO 1063 in the CVM1, CV-series or CS/CJ-
series PLC. CIO 1064 to CIO 1199 cannot be linked with C200HX/HG/HE
or CQM1H-series PLCs in this way.

IR/CIO Area

Available for the data links

DM Area

Not available for the data links

Available for the data links

Example:

Example:

to

CVM1, CS/CJ, or CV-series PLCs

0

235

to

0


235

to

2555

to

DM000



DM5999

to

to

DM000



DM5999

DM24575

Not available for the data links

CVM1, CS/CJ, or CV-series PLCs

C200HX/HG/HE or
CQM1H-series PLCs

C200HX/HG/HE or
CQM1H-series PLCs

Cannot be directly linked
with C200HX/HG/HE words.

LR00

LR63

to

1000

1063

to

1064

1199

to

CVM1, CS/CJ, or CV-series PLCs

CIO words of CVM1, CS/CJ, or CV-series PLCs
= (LR words of C200HX/HG/HE or
CQM1H-series PLCs) + 1000

C200HX/HG/HE or
CQM1H-series PLCs

Advertising