Omron CQM1H-CLK21 User Manual

Page 144

Advertising
background image

121

Setting Data Links

Section 5-2

Note a) The total number of words in data link send and receive areas

must not exceed 8,000 per node.

b) The following values must be satisfied for each node for the data

link area 1 and area 2 so that the final word in the data link does
not go beyond the last word in the PLC memory area.

First data link sta-
tus word

Set the first word to store data link status. An area of 16 words is
used.

IR Area:

IR 001 to IR 232

LR Area:

LR 00 to LR 48

DM Area:

DM 0000 to DM 5984

EM Area:

EM 0000 to EM 6128 (EM must be installed)

When IR 000 is specified or when the default setting (

–––––

) is

left unchanged, the default first status word will be used. Refer
to 5-4 Checking Data Link Status for details.

Area 1

Data link
start word

IR Area:

IR 000 to IR 247

LR Area:

LR 00 to LR 63

DM Area:

DM 0000 to DM 5999

EM Area:

EM 0000 to EM 6143 (EM must be installed)

The same memory area cannot be set for both area 1 and area
2. Set different memory areas.

Number of
words

Remote nodes: 0 to the number of source words

Set the number of words to be received.

Local node:

0 to 1,000
Set the number of words to be transmitted.

The total number of words in area 1 and area 2 in each node
must not exceed 1,000.

The numbers of words in both area 1 and area 2 in each node
must not be set to 0.

Offset

Remote nodes: 0 to one less than number of source words

Set the offset for the data to be received.

Local node:

Cannot be set.

This setting is not required if an offset is not used.

Area 2

Data link
start word

IR Area:

IR 000 to IR 247

LR Area:

LR 00 to LR 63

DM Area: DM 0000 to DM 5999

EM Area: EM 0000 to EM 6143 (EM must be installed)

The same memory area cannot be set for both area 1 and area
2. Set different memory areas.

Number of
words

Remote nodes: 0 to the number of source words

Set the number of words to be received.

Local node:

0 to 1,000
Set the number of words to be transmitted.

The total number of words in area 1 and area 2 in each node
must not exceed 1,000.

The numbers of words in both area 1 and area 2 in each node
must not be set to 0.

Offset

Remote nodes: 0 to one less than number of source words

Set the offset for the data to be received.

Local node:

Cannot be set.

This setting is not required if an offset is not used.

Setting item

Setting range

Advertising