217

Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs

Section 6-6

Response Block

Parameters

Program no. (command and response): Set to 0000 (Hex).

Beginning address (command and response): Set an relative byte address
with 00000000 (Hex) as the starting address. The beginning word must be an
even number. The address set in the command will be returned in the
response.

No. of bytes (command and response): The number of bytes in an even
number 07C6 (Hex) (1990 in decimal) or smaller. The number of bytes actu-
ally read will be returned in the response. Bit 15 will be ON (1) in the response
block when the last word data of the program area is returned.

Data (response): The data in the specified program area will be returned in
sequence starting from the beginning word.

Note If the designated number of bytes is larger than the program area, the pro-

gram will be read through the final address and a response code indicating an
address range error or response length error will be returned.

6-6-7

PROGRAM AREA WRITE

Writes data to the specified number of consecutive program area words start-
ing from the specified word. A maximum of 1,990 bytes can be written with
each command. To write larger amounts of data, use multiple commands and
specify the beginning word and number of words for each. The data is written
to the program area at the machine language (object code) level.

Command Block

Response Block

Parameters

Program no. (command and response): Set to 0000 (Hex).

Beginning word (command and response): Set a relative byte address with
00000000 (Hex) as the starting address. The beginning word must be an even
number. The address set in the command will be returned in the response.

03

06

00

00

Beginning address

Data

Program

no.

No. of

bytes

Response

code

Command

code

1,990 bytes maximum

Bits 0 to 7 (second byte)

Bits 8 to 15 (first byte)

Bit 15 OFF (0): Without last word data
Bit 15 ON (1): With last word data
Bits 0 to 14: No. of bytes read

03

07

Program

no.

Beginning word

Data

No. of

bytes

00

00

Command

code

1,990 bytes maximum

03

07

Beginning word

Program

no.

00

00

No. of

bytes

Response

code

Command

code