C200HX/HG/HE Controller Link Units

Section 4-3

4-3-1

Overview

Node Address

Baud Rate and Operating Level

Baud Rate

Note

Factory default setting is in bold.
Always leave pin 3 OFF.

Operating Level

Terminating Resistance

4-3-2

Node Addresses

Set the node addresses of each Unit on the Network using the rotary switches
on the front of the Unit. The node address is used to identify each node in the
Network can be set to any number between 01 and 32.

1

CLK21

X10

1

X10

0

SW1

ON

BD

H

BD

L

SHLD

RUN
ERC
INS
SD

TER
ERH
M/A
LNK

RD

TER
SW

#0, #1

1

2

3

4

RSV

BAUD
RATE

0

1

23

4

1

X10

1

X10

0

SW1

ON

#0, #1

1

2

3

4

RSV

BAUD
RATE

0

1

23

4

NODE NO.

Setting range

Nodes

01 to 32 (default is 01)

All nodes in the Network

Pins

Baud rate

Maximum

transmis-

sion dis-

tance

Nodes

Pin 1

Pin 2

OFF OFF

2 Mbps

500 m

Set same
rate for all
nodes in the
Network.

ON

OFF

1 Mbps

800 m

OFF

ON

500 Kbps

1 km

ON

ON

Cannot be set.

Pin 4

Operating

level

Nodes

OFF
(factory
default)

Level 1

All nodes in the Network

Set so that only one Communi-
cations Unit is set to the same
level in the same PLC.

ON

Level 0

Bottom

switch

Terminating

resistance

Nodes

OFF
(factory
default)

Not connected

All nodes in the Network

Turn ON the terminating resis-
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.

ON

Connected

1's digit

10's digit

NODE NO.

X10

1

X10

0

0

1