2-3 communications specifications, Communications specifications – Omron CQM1H-CLK21 User Manual

Page 37

Advertising
background image

14

Specifications and Configurations

Section 1-2

1-2-3

Communications Specifications

Wired System

Note

1.

The maximum distance between nodes depends on the connector and ca-
ble processing methods.

2.

At least one Repeater Unit is required to construct networks that uses a
node address higher than 32. The following Controller Link Units/Support
Boards must also be used, and the Wired Network 62 Node Enable Bit of
the DM Parameter Area software switch of all nodes must be turned ON
(62 nodes max.).

CS1W-CLK21-V1, CJ1W-CLK21-V1, and 3G8F7-CLK21-V1

3.

62,000 data link words applies to configurations of 62 nodes.

Items

Specifications

Communications method

N:N token bus

Code Manchester

code

Modulation Baseband

code

Synchronization

Flag synchronization (conforms to HDLC frames)

Transmission path form

Multi-drop bus

Baud rate and maximum
transmission distance

The maximum transmission distance varies with the baud rate as follows:

2 Mbps:

500 m

1 Mbps:

800 m

500 Kbps: 1 km

Media

Specified shielded twisted-pair cable
Number of signal lines: 2, shield line: 1

Node connection method

PLC: Connected to a terminal block

IBM PC/AT or compatible: Connected via a special connector (included)

Maximum number of nodes 32 or 62 nodes (See note 2.)

Communications functions

Data links and message service

Number of data link words

Transmission area per node:

1,000 words (2,000 bytes) max.

Data link area (send/receive words) per node
CS/CJ Series:

20,000 words max. (unit Ver. 1.2 or later)
12,000 words max. (pre-Ver. 1.2)

C200HX/HG/HE, CVM1/CV, CQM1H: 8,000 words max.
Personal computer: 32,000 or 62,000 words max. (See note 3.)

Number of data link words in one network (total transmission):

32,000 words (64,000 bytes) or 62,000 words max. (See note 3.)

Data link areas

Bit-access areas (IR, AR, LR, CIO), DM Area (DM), and extended DM Area (EM)

Message length

2,012 bytes max. (including the header)

RAS functions

Polling node backup function

Self-diagnosis function (hardware checking at startup)

Echoback test and broadcast test (using the FINS command)

Watchdog timer

Error log function

Error control

Manchester code check

CRC check (CCITT X

16

+ X

12

+ X

5

+ 1)

Advertising
This manual is related to the following products: