Omron CQM1H-CLK21 User Manual

Page 95

Advertising
background image

72

Wiring

Section 3-3

8.

Do not place any object on the power cable.

9.

Check that connectors are correctly attached before using the Unit.

Power Supply Specifications

The power supply to the Repeater Unit must meet the following specifications.

The following Power Supply Unit is recommended:

OMRON S82K Series

Laying Optical Cable (CS1W-RPT02/03 Only)

Optical fiber cable (H-PCF or GI) can be used to create an optical connection
in part of a wired network.

CS1W-RPT02 (H-PCF)

Note

1.

Always use the specified Optical Fiber Cables.

2.

The maximum distance between nodes depends on how the cable is con-
nected. For details, refer to the applicable Optical Fiber Cable (H-PCF)
manual.

Connection Procedure

Use the following procedure to connect Optical Fiber Cables to a Unit.

1,2,3...

1.

Tighten screws in the mounting brackets so that the through-holes on the
terminal are on the top and bottom and then affix hexagonal nuts from the
opposite side of the terminal.

2.

Insert bushing to the mounting bracket and secure the Unit with screws.

3.

Pass the tension member through the through-holes, and tighten the ter-
minal screws to affix the tension member.

4.

Affix the cable to the mounting bracket so that it is clamped by the bracket.

Item

CS1W-RPT01

Wire-to-Wire

Repeater Unit

CS1W-RPT02

Wire-to-Optical (H-

PCF) Repeater Unit

CS1W-RPT03

Wire-to-Optical (GI)

Repeater Unit

Power supply volt-
age

24 V DC

Allowable power
supply voltage
range

20.4 to 26.4 V DC (24 V DC,

15% to 10%)

Current consump-
tion

24 V DC at 60 mA
max.

24 V DC at 60 mA
max.

24 V DC at 70 mA
max.

Inrush current

2.5 A max. (24 V DC with rise time 5 ms)

H-PCF cable

SL1

SL2

SL1

SL2

Wired Controller
Link Unit

Wired Controller
Link Unit

CS1W-RPT02
Repeater Unit

CS1W-RPT02
Repeater Unit

Advertising
This manual is related to the following products: