C200hx/hg/he plcs – Omron CQM1H-CLK21 User Manual

Page 219

Advertising
background image

196

Using the Message Service

Section 6-3

C200HX/HG/HE PLCs

DIFU(13) 31001

31000

25204

@XFER(70)

#0010

000

DM 0010

@MOV(21)

#000A

DM 0000

31000

R

S

KEEP(11)
31000

00000

25204

31002

31001

@MOV(21)

#9500

DM 0001

@MOV(21)

#0003

DM 0002

@SEND(90)

DM 0010

DM 0020

DM 0000

00200

31000

25203

Control Data Preparation

Turns ON to indicate transmission error.

DM 0000 0 0

0 A

10 send words*

DM 0001 9 5

0 0

Operating level 1**

DM 0002 0 0

0 3

Node 3, Unit 0 (a PLC)

Transfers the 10 words beginning at IR 000 to the 10
words beginning at DM 0010.

Transfers the 10 words beginning at DM 0010 of the
source node to the words beginning with DM 4000
(specified by DM 0020 and DM0021) at node address 3.

Creates reset input.

* No destination network address specified
** Response required, 5 retries, direct designa-
tion, monitoring time: default

IR 31000 remains ON while the SEND instruction is
being executed, and it turns OFF when instruction
execution has been completed.

Beginning Word for Indirect Receiving by
Destination Node

DM 0020 0 5

0 0

DM 0021 4 0

0 0

Beginning word for
receiving (by destina-
tion node) = DM4000
(05: DM designation)

Execution
condition

@MOV(21)

#0500

DM 0020

@MOV(21)

#4000

DM 0021

Network Instruction Error Flag

(Continued on the next page)

The transmission program will run when IR 00000
turns ON, provided that the Network Instruction En-
abled Flag is ON and the RECV instruction has not
been executed.

Advertising
This manual is related to the following products: