Omron CQM1H-CLK21 User Manual

Page 171

Advertising
background image

148

Setting Data Links

Section 5-2

Note a) The total number of words in data link send and receive areas

must not exceed 8,000 per node.

b) The following values must be satisfied for each node for the data

link area 1 and area 2 so that the final word in the data link does
not go beyond the last word in the PLC memory area.

(Data link start word – 1) + Total number of send/receive
words in area

2555 (CIO Area)
199 (LR Area)
8191 (DM Area for CV500/CVM1-CPU01)
24575 (DM Area for other CPU Units)
32765 (EM Area)

c) When using area 1 only, set the data link start word, type, and

the number of send words of area 2 to 0.

d) When using area 2 only, set the data link start word, type, and

the number of send words of area 1 to 0.

e) The startup node must be registered as a participating node of

the data links. If not, the data links will not start.

Note

1.

When data links are automatically created for networks containing
C200HX/HG/HE, CS/CJ-series, CVM1, CV-series, and CQM1H-series
PLCs, the linkable area is restricted to the area of the C200HX/HG/HE or
CQM1H-series PLC because it is smaller than that of CVM1, CV-series or
CS/CJ-series PLCs.

Send size (number of
words) for node of area 2

Set the number of words in BCD between 0 and 1,000.

The total number of send words of area 1 and area 2
must not exceed 1,000.

When area 2 is not used, set to 0.

First data link status word Set in BCD the first word used for storing data link status.

An area of 16 words is used for storing status.

0 (*) or CIO 0001 to CIO 2540

Status is stored in the CIO area only.

*: When 0 is set, the status is saved in CIO 1500 + unit

number x 25 (+ 7 to + 22).

Nodes participating in the
data links

Set to ON (1) the bits corresponding to the nodes partici-
pating in the data links.

The data link will not start unless the startup node itself is
set as participating node.

The data link will not start if the node is set to a parameter
exceeding the “maximum node address” of the network
parameter.

Item

Setting range

Advertising