11. If the LR Area in the C200HX/HG/HE or CQM1H-series PLC is automati-

cally set for a data link with a CVM1, CV-series PLC or CS/CJ-series PLC,
the LR words will be linked to CIO 1000 to CIO 1063 in the CVM1, CV-se-
ries or CS/CJ-series PLC. CIO 1064 to CIO 1199 cannot be linked with
C200HX/HG/HE or CQM1H-series PLCs in this way.

C200HX/HG/HE Startup Node

Set the following DM Parameter Area of the PLC of the startup node.

Settings

Cannot be directly linked
with C200HX/HG/HE words.

LR00

LR63

to

1000

1063

to

1064

1199

to

CS/CJ-series PLCs

IR words of CS/CJ-series PLCs
= (LR words of C200HX/HG/HE or
CQM1H-series PLC) + 1000

C200HX/HG/HE or
CQM1H-series PLCs

Data link mode
Set to 01 for automatic setting.
(00 is for manual setting. Other values are invalid.)

Area 1 data link start word (BCD)

Area 1 type

Number of send words per node of area 1 (BCD)

Rightmost 4 digits of data link start word of area 2 (DM area) (BCD)

Leftmost digit of data link start word of
area 2 (BCD)

First data link status word (BCD)

BCD: Set the value as binary-coded decimal.

Nodes to participate in the data links

The numbers indicate node numbers.
The value assigned indicates whether the
node is to participate in the data links.
Participate: 1
Not participate: 0

Word N

0: Always specify 0.
– : By other setting

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

15

8

7

0

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

N+1

N+2

N+3

N+4

N+5

N+6

N+7

N+8

32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17

N+9

0

0

0

0

0

0

0

0

0

0

0

N:

Level 0 = DM 6400

Level 1 = DM 6420

Area 2 type

Number of send words per node of area 2 (BCD)

00

Item

Setting range

Data link mode

Specify automatic (01).

Area 1 data link start
word

Set the word address in BCD.

IR Area: IR 000 to IR 235, IR 300 to IR 511

LR Area: LR 00 to 63

Area 1 type

Set the area for area 1 in BCD.

IR Area: 80

LR Area: 86

Area 1 not used: 00