CS-series Controller Link Units

Section 4-1

4-1

CS-series Controller Link Units

The following settings are required for a Controller Link Unit used with a CS-
series PLC.

4-1-1

Overview

Unit Number

Node Address

Baud Rate

Note Factory default setting is in bold.

Always leave pins 3 and 4 OFF.

Terminating Resistance

4-1-2

Unit Number

Set the unit number for each Unit using the rotary switches on the front of the
Unit. The unit number is used to identify a CPU Bus Unit within the PLC. Any
unit number can be set between 0 and F in hexadecimal (00 to 15 in decimal)

.

Item

Switch

Page

Unit number

Unit number setting switch

86

Node address

Node address switches

87

Baud rate

Baud rate, pins 1 and 2

88

Terminating resistance

Terminating resistance switch

89

CLK21-V1

Setting range

Nodes

01 to F (default is 0)

All nodes in the Network

Setting range

Nodes

01 to 32 (default is 01)

All nodes in the Network

Pins

Baud rate

Maximum

transmission

distance

Nodes

Pin 1

Pin 2

OFF OFF

2 Mbps

500 m

Set same
rate for all
nodes in the
Network.

ON

OFF

1 Mbps

800 m

OFF

ON

500 Kbps

1 km

ON

ON

Cannot be set.

Front switch

Terminating

resistance

Nodes

OFF
(factory default)

Not connected

All nodes in the Network

Turn ON the terminating resis-
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.

ON

Connected

Note: The factory default settings are shown above.