286

Troubleshooting Using Indicators

Section 9-1

Node Cannot Participate
in Data Link

The following table describes the LNK and M/A indicators when a node can-
not participate in the data links.

Data link participation depends on the Controller Link Unit operating normally
and participating in the Network. Refer to Troubleshooting with RUN, ERC,
ERH and INS Indicators
earlier in this section and check Unit operation before
using the following table.

Indicators

Probable cause

Probable remedy

LNK

M/A

Lit

---

Data link operating normally.

---

Flashing

---

There is an error in the data
link tables.

If the ERH indicator is lit, reset
the data link tables.

When manual setting is used,
either data link tables have not
been created for the startup
node or there is an error in the
data link tables.

Refer to 5-2-2 Manual Setting
and set data link tables for the
startup node.

When automatic setting is
used, either the data link
parameters for the startup
node have not been set or
there is an error in the data link
tables.

Refer to 5-2-4 Automatic Set-
ting
and set the automatic
parameters for starting the
data links.

Automatic setting is used with
1:N allocations, but the device
does not support this function.

Use a Controller Link Unit that
supports automatic data link
creation with 1:N allocations.
Refer to Automatic Setting on
page 129 f
or details.

Not lit

Lit

Manually set data links are
already operating on the same
Network.

Stop the manually set data
links that are operating and
restart the data links.

Not lit

Not lit

Automatically set data links
are already operating on the
same Network.

Stop the automatically set data
links that are operating and
restart the data links.

There is an error in the startup
node PLC.

Refer to the PLC’s operation
manual and correct the error. If
the error reoccurs, replace the
PLC.