299

Status Area and Troubleshooting

Section 9-2

9-2-2

C200HX/HG/HE Controller Link Units

The status of the Unit and Network is indicated in the following manner in the
PLC.

Status Area

Duplicate Operating Levels/Refresh Error: AR 00

Routing Table Error/Unit Restart Bits: AR 01

Network Participation Status: AR 08, AR 09, AR 12, AR 13

Communications Controller Hardware Error, EEPROM Error: AR 11, AR 15

Service Time: AR 16, AR 17

Operating Level Connection Status, Inconsistent Network Parameters: AR 24

A bit will be turned ON (1) the
next cycle when
1) The same operating level is

set more than once or

2) A refresh error occurs

between the Controller LInk
Unit and the PLC's CPU Unit.

Operating level 1
Operating level 0

Operating level 1
Operating level 0

1: Routing table error

Resets the Controller Link Unit.
Turn ON (1) and then OFF (0)
to reset Unit.

Operating level 1

Operating level 0

Operating level 0
AR 08
AR 09

Operating level 1
AR 12
AR 13

The numbers in the squares indicate node addresses.
The corresponding node participation status is as follows:
0: Not part of network
1: Part of network

Operating level 0
AR 11

Operating level 1
AR 15

1: Communications controller hardware error

1: EEPROM error

Operating level 0
AR 16

Operating level 1
AR 17

The service time for each PLC cycle is calculated by the PLC
and displayed in 0.1-ms units in 4-digit BCD.

Operating level 1

Operating level 0

1: Network parameters do not match

1: Connecting to the operating level

Operating level 1
Operating level 0