63

Unit Installation

Section 3-2

CJ-series PLCs

Up to a total of four Controller Link Units for CJ-series PLCs can be connected
in a CPU Rack or a Expansion Rack. (Be sure to secure the Units with the top
and bottom sliders.)

Note When installing several CJ-series CPU Bus Units at the same time, a total of

16 CJ-series CPU Bus Units maximum may be installed.

Up to eight CS/CJ-series Controller Link Units with unit version 1.2 or later
can be connected to a single CPU Unit. When connecting multiple Controller
Link Units to the CPU Unit, consider the current consumption of the CPU Unit
and each CPU Bus Unit before selecting the Power Supply Unit. For details on
Controller Link Unit current consumption, refer to

Controller Link Unit Models

and PLCs on page 16

. For details on current consumption of each Unit, refer

to the SYSMAC CJ Series Programmable Controllers Operation Manual
(W393).

The following table provides an example of current consumption

P
S

C
P
U

I

C

P
S

I
I

P
S

I
I

P
S

I
I

Of these slots, installation
is possible in up to 8 slots
(unit Ver. 1.2 or later).
Installation in up to 4 slots
is possible for pre-Ver. 1.2
Units.

CPU Rack

CJ-series Expansion
Rack

10 Unit max.

End Cover

CJ-series Expansion
Rack

10 Unit max.

End Cover

CJ-series Expansion
Rack

10 Unit max.

End Cover

10 Unit max.

End Cover

PS: Power Supply Unit
CPU: CPU Unit
IC: I/O Control Unit
II: I/O Interface Unit