Handling Precautions

Section 9-6

2.

Detach the communications cables and the Bus Connection Unit attached
to the Controller Link Unit to be replaced and remove the Unit.

3.

Mount the new Controller Link Unit in the PLC and connect the communi-
cations cables and the Bus Connection Unit. (Refer to SECTION 3.)

4.

Set the node address, baud rate, operating level (front DIP switch,
C200HX/HG/HE only) and the terminating resistance for the new Unit to
the same settings as the previous Unit. (Refer to SECTION 4.)

5.

Turn ON only those PLC for which Units were replaced.

6.

Set the following software switches on the new Controller Link Unit using
the Programming Device.

• Polled node/ polling nodes: ON (polled node)

• EEPROM Clear But: ON (EEPROM Clear)

7.

Turn off the power again to PLCs for which the Controller Link Unit has
been changed.

8.

If the CPU Unit DIP switch pin 5 of the PLC for which the Controller Link
Unit has been replaced is ON (automatic transmission), set to OFF (no au-
tomatic transmission.)

9.

Turn off all nodes in the Controller Link Network.

10. If the Controller Link Support Software can be operated, use it to read the

network parameters and make sure the Network is operating normally.

11. If the data links are not activated automatically, activate the data link from

the data link startup node.

12. If the Controller Link Support Software can be operated, use it to check

that the data links are operating normally by monitoring the data link status.

13. Return the software switches set in step 6. in the new Controller Link Unit

to the following settings using the Programming Device.

• Polled node/polling node: OFF (polling node)

• EEPROM Clear Bit: OFF (Do not clear EEPROM)

Check the above if the Controller Link Support Software can be used.

14. If DIP switch pin 5 on the CPU Unit was switched from ON to OFF in set

8., turn the PLC OFF once, return the DIP switch to ON, and turn the power
ON again.

CS/CJ-series, CVM1, and CV-series Controller Link Units

Note CS/CJ-series, CVM1, and CV-series Controller Link Unit data is stored in the

EEPROM of the CPU Unit. For this reason even if the Controller Link Unit is
replaced, on the hardware settings must be made to return all settings to their

Operating level 0
DM 6400

Operating level 1
DM 6420

– : Other settings

EEPROM Clear Bit

0: Do not clear EEPROM
1: Clear EEPROM

Polled node/polling node 0: Polling node

1: Polled node

DM 6400

C200HX/HG/HE

CQM1H Series

–: Other settings

EEPROM Clear Bit

0: Do not clear EEPROM
1: Clear EEPROM

Polled node/polling node 0: Polling node

1: Polled node

Operating level 0
DM 6400

Operating level 1
DM 6420

DM 6400

C200HX/HG/HE

CQM1H Series