Omron CQM1H-CLK21 User Manual

Page 339

Advertising
background image

316

Error Log

Section 9-3

0101
Hex

Transmission failed; local node
not in Network

Command block
Bits 0 to 7:

Source node address

Bits 8 to 14:

Source Network
address

Bit 15:

OFF

Response block
Bits 0 to 7:

Destination node
address

Bits 8 to 14:

Destination Network
address

Bit 15:

ON

(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)

Refer to page 276
Troubleshooting
Using Indicators
and
place the local node
into Network.

No

All

0103
Hex

Transmission failed; retry count
exceeded

Using the Controller
Link Support Soft-
ware or FINS
commands, run
echoback test and
check operating envi-
ronment if errors
occur.

No

All

0104
Hex

Transmission failed; maximum
number of frames exceeded.

Reduce the number
of events per com-
munications cycle or
increase the maxi-
mum number of
network parameter
frames.

No

All

0105
Hex

Transmission failed; node
address incorrect

Refer to 4-2 CJ-
series Controller Link
Units
or
4-4 CVM1
and CV-series Con-
troller Link Units
an
d
check node address
settings to be sure
they are within range
and unique.

No

All

0106
Hex

Transmission failed; redundant
node address

Correct node
addresses so that
they are unique
within the same
Network.

No

All

0107
Hex

Transmission failed; destination
node not in Network

Refer to 9-1 Trouble-
shooting Using Indi-
cators
a
nd place
destination node into
Network.

No

All

0108
Hex

Transmission failed; specified
Unit does not exist

Refer to 4-4 CVM1
and CV-series Con-
troller Link Units
an
d
check unit address
and unit number of
destination.

No

All

Error

code

Contents

Detail code

Correction

Written to

EEPROM

Applicable

PLC

1st byte

2nd byte

Advertising