Relay Control Logic

User Guide: Falcon FMS

126

970 484-6510

www.rletech.com

active until the alarm returns to normal. The time is configured on each relay configuration page. This gate
can also be set for latching—the relay will stay active until it is manually reset by a user.

Inverter Gate
This gate can invert the relay activation. This allows the relay to be used in a "supervised" mode. In this
mode, if the FMS loses power, the relay will close. The gate is configured on each relay configuration
page.

Schedule
Each relay can be activated by either of the two schedules in the FMS. During the scheduled time-of-day
the relay is activated. The schedule option is configured on each relay configuration page.

Keypad
Each relay can be controlled by a 3x4 keypad instead of the alarm inputs. The keypad option is configured
on each relay configuration page.

DTMF
Each relay that can be programmed to be controlled by the keypad can also be controlled from a DTMF
signal received on the phone line.

Force On/Off
Each relay can be forced to ON or OFF. This will override any alarm or keypad control of that relay until
the relay operation has been restored.