2-2.8 Modbus EIA485 Connections

The FMS can function as a Modbus Master or Slave over an EIA485, 2-wire hardware connection. The
EXP-MBCS option is required to allow the FMS to function as a Modbus Master. This option must be set
at the factory for an FMS to have Modbus capabilities.

P4 RJ11

TELCO

P5 RJ45

NETWORK

IOIOI

P3 RS232

COM2

IOIOI

P2 RS232

COM1

SW1

+ - GND

RS485 COM1

IOIOI

COM1 SELECT

K2 RX RX 485

K1 TX TX 232

RELAY COM2 COM1

48

5

T

E

RM

SEL

M

/S

TB5 KEYPAD

TB4

NC NO C

RELAY 1

NC NO C

RELAY 2

1 2

ON

(Female)

(Male)

<

N

am

e/

S

la

ve

A

dd

re

ss>

S

hie

ld

TX-

/R

X

-

TX+

/R

X

+

M

odb

us

De

vi

ce

<

N

am

e/

S

la

ve

A

dd

re

ss>

S

hie

ld

TX-

/R

X

-

TX+

/R

X

+

<

N

am

e/

S

la

ve

A

dd

re

ss>

S

hie

ld

TX-

/R

X

-

TX+

/R

X

+

M

odb

us

De

vi

ce

M

odb

us

De

vi

ce

100 Ohm

Termination

Resistor

Switch #1 = On,

Inserts 100 Ohm

Termination Resistor

Figure 2-10: FMS EIA485 Connection

2-2.9 Modbus EIA232 Connections

The FMS can function as a Modbus Master or Slave over an EIA232 hardware connection. The EXP-
MBCS option is required to allow the FMS to function as a Modbus Master. The EIA232 port is configured
as a DTE device.