RLE Falcon EM User Manual

Page 89

Advertising
background image

User Guide: Falcon FMS

Communication

www.rletech.com 970

484-6510

75

Figure 5-15: Modbus Register Configuration Menu


Selecting a link to an individual register displays the configuration options for that register; see Figure 5-
16. Instructions for completing the options on this page are described below.

Figure 5-16: Individual Modbus Configuration Screen


Unit: Enter the Slave Unit Number. This is NOT the Slave address, but the Slave Unit Number shown on
the Modbus Slave Unit Configuration page; see Figure 5-13, pg. 73.

Register: Enter the Register Number for the data to be read. The Register Number is located on the Slave
Units Modbus Register Map; see section 5-8.1 Slave Register Map, pg. 80.

Type: Select the Data Type of the Register.

Unsigned Int

Signed Int

Long

Float

Alarm Bit/ ON= ALARM

Alarm Bit/ OFF=ALARM

Status Bit – No Log

Status Bit – Logged

Coil Status

Input Status

NOTE:

Refer to the manufacturers equipment guide for the register numbers and the data
type.