User Guide: Falcon FMS

80 970

484-6510

www.rletech.com

Figure 5-22: Modbus BCM Unit Configuration Page

5-8

ADDITONAL MODBUS INFORMATION

5-8.1 Slave Register Map

Table 5-1: Slave Register Map

Register Desc

Range

40001

Input #1 value

-32678 - 32767

.. ..

..

40104

Input #104 value

-32678 - 32767

40105

Internal Temperature Sensor

-32678 - 32767

40106

Internal Humidity Sensor

-32678 - 32767

40107-40187 Reserved

40188-40193 MAC

address

00:90:5b:01:01:01

40194-40197 IP

address

10.0.0.203

40198

Model Number

100

40199

Firmware Version

73

40200

Number of Alarms Present

0-65535

40201

Input #1 alarm bit map

0 - 0x0010

.. ..

..

40304

Input #104 alarm bit map

0 – 0x0010

40305

Internal Temperature Sensor -
alarm bit map

0 – 0x0010

40306

Internal Humidity Sensor - alarm
map

0 – 0x0010

40307-40400 Reserved

40401

Input #1 config code

0 - 7

.. ..

..

40504

Input #104 config code

0 – 7