Programming Function Blocks and Features

Video Recorder – User Manual

105

4.11 Program Discrete Outputs

Discrete Output function blocks control the relay or open collector output hardware. The Program
Discrete Outputs menu item will appear if a Discrete Outputs board is installed.

ATTENTION

If a discrete output has been assigned to a time proportioning output (DAT), it will not be programmable here.
See "OUTPUT RELAY" in Table 4-13.

Select a DO to program, then program the prompts in Table 4-15. See Table 4-2 for additional prompts.

Table 4-15 Discrete Output Prompts

Prompt

Range/Selections

Definition

ACTION STATE

NORMAL, INVERT

Determines whether the relay will normally be energized or
de-energized when the DO’s Input is ON(1). To select
energized when ON, enter NORMAL (not inverted). To select
energized when OFF, enter INVERT (inverted).

INPUT

OFF, discrete parameter, 0,
1

Source of the Discrete Output.

EVENT ENABLE

NONE, RISING, FALLING,
BOTH

Determines whether changes in DO’s status can be recorded
as events in data storage. For storage to occur, Data
Storage must also be programmed to store Events.

NONE - status changes are not stored

RISING - OFF(0)-to-ON(1) changes can be stored

FALLING - ON(1)-to-OFF(0) changes can be stored

BOTH - Rising and falling changes can be stored