Honeywell VRX180 User Manual

Page 148

Advertising
background image

Programming Function Blocks and Features

Video Recorder – User Manual

134

Table 4-41 Advanced Splitter Prompts

Prompt

Range/Selections

Definition

RANGE LOW

RANGE HIGH

OFF or number

Enter the output's display limits. Output is not clamped or
flashed when it exceeds these limits.

INPUT

OFF, analog parameter,
number

Input source. Typically, this is the output value (OV) of a
Split Output type of loop.

FEEDBACK #1

OFF, AOn BC, LPn BC

Select the back calculation value (BC) of the analog output
assigned to the A1, A2, and A3 outputs, respectively.

FEEDBACK #2

FEEDBACK #3

OUT#1 IN LO LIM

OUT#1 IN HI LIM

OFF or number

Enter a range for A1's input. Defauts are 0 for low limit & 30
for high limit. When input is between these values, A1
output is scaled between OUT#1 OUT LO LIM & OUT#2
OUT HI LIM.

OUT#1 OUT LO LIM

OUT#1 OUT HI LIM

OFF or number

Enter OFF or a range for A1’s output. Defaults are 0 for low
limit & 100 for high limit. Scales A1 output.

OUT#2 IN LO LIM

OUT#2 IN HI LIM

OFF or number

Enter a range for A2’s input. Defaults are 30 for low limit &
60 for high limit. When input is between these values, A2
output is scaled between OUT#2 OUT LO LIM & OUT#2
OUT HI LIM.

OUT#2 OUT LO LIM

OUT#2 OUT HI LIM

OFF or number

Enter OFF or a range for A2’s output. Defaults are 0 for low
limit & 100 for high limit. Scales A2 output.

OUT#3 IN LO LIM

OUT#3 IN HI LIM

OFF or number

Enter a range for A3’s input. Defaults are 60 for low limit &
90 for high limit. When input is between these values, A3
output is scaled between OUT#3 OUT LO LIM & OUT#3
OUT HI LIM.

OUT#3 OUT LO LIM

OUT#3 OUT HI LIM

OFF or number

Enter OFF or a range for A3’s output. Defaults are 0 for low
limit & 100 for high limit. Scales A3 output.