4.23 Load/Store Configuration

Instrument configurations can be stored to and loaded from floppy disk. The front door must be closed.
Configurations have filename extension .LNC.

Table 4-69 describes the Load/Store Config prompts.

Table 4-69 Load/Store Config Files Prompts

Prompt

Range/Selections

Definition

STORE CONFIG TO

DISK

FILE01 CYCLE01

DRYER01 PROD01

RECORD01 TANK01

UNIT01 LOOP01

REACTR01 CONFIG01

KILN01 VESSEL01

CALIB01 WCHEM01

PRESS01 FURNCE01

DEMIN01 CONTRL01

BATCH01 FERMTR01

LEHR01 LINE01

STRLZR01 OVEN01

ZONE01

Specify a filename and number (01-99) for the
configuration. Press Enter to store the configuration.

LOAD CONFIG

FROM DISK

Select a configuration
filename.

First you must clear the instrument’s configuration memory.
Press Enter to clear, or Menu to abort and exit the menu.
Once the memory is clear, select a filename from the floppy
disk. Press Enter to load the configuration into the
instrument.

ATTENTION

Only function blocks that have been programmed are loaded to the instrument. Function blocks in the receiving
instrument are not replaced unless the incoming function blocks are programmed differently. For example, if the
instrument has AI1 and AI2 programmed, and the configuration being loaded from the floppy contains AI3 only,
then AI1 and AI2 are undisturbed on the instrument and AI3 is added. If the configuration being loaded contains a
different AI2 and a new AI3, then AI1 is undisturbed, AI2 is replaced by the different AI2, and AI3 is added.