Programming Function Blocks and Features

Video Recorder – User Manual

117

Logic

The input or inputs are processed by a logic operator. Call the result of this logic operation “Result”.
Result is a pulse that goes ON(1) when the logic is true, and OFF(0) when the logic is not true. Result
is then processed according to the specified condition type and condition time. The final output is a
discrete pulse CVn OS. See Figure 4-5.

LOGIC

OPERATOR

Inputs

A
B
C
D
E
F
G
H

Result

CONDITION

TYPE

&

CONDITION

TIME

CVn OS

Figure 4-5 Logic Signal Flow

Table 4-25 describes the Logic prompts. See Table 4-2 for additional prompts.

Table 4-25 Logic Prompts

Prompt

Range/Selections

Definition

OPERATOR

AND, OR, XOR, RESET/SET FF,
TOGGLE/FF, ONE SHOT, PASS

See Table 4-26.

INPUT A

OFF, discrete parameter, 0, 1.

Program at least 2 inputs. Only inputs
programmed with parameter, 1, or 0 are processed
with the operator.

INPUT B

INPUT C

INPUT D

INPUT E

INPUT F

INPUT G

INPUT H

CONDITION TYPE

NONE, DELAY, EXTEND, PULSE,
RT PULSE

See Table 4-20 on page 111.

CONDITION TIME

OFF or number

Enter number of seconds of condition time. See
Table 4-20 on page 111.