Setpoint Profiler

Video Recorder – User Manual

196

Editing Segments

Use the following prompts to map out each segment’s value, time, and events. Up to 63 segments are
programmable per profile.

Table 5-6 Edit Segments Prompts

Prompt

Range/Selections

Definition

NEXT SEGMENT

Select this to edit the next segment.

PREVIOUS SEGMENT

Select this to edit the previous segment

VALUE

OFF or number

This prompt is active for soak segments
and value/duration ramp types. Enter the
value of the segment.

AUX VALUE

OFF or number

This value is an auxiliary soak output of
the profile. The output is identified as
SPn A1 and remains constant for the
duration of the segment.

TIME

OFF or Positive number

The purpose of the number entered here
depends on the ramp type of the profile.
See 4 types of ramp segments on page
178 for details.

GUAR SOAK #1

ON or OFF

ON means the profiler will Hold during this
segment if deviation between PV #1 and
the profiler output exceeds the
guaranteed soak limits in Table 5-5. OFF
means the profiler will not Hold during this
segment due to deviation. See
Guaranteed Soak on page 182 for details.

GUAR SOAK #2

ON or OFF

ON means the profiler will Hold during this
segment if deviation between PV #2 and
the profiler output exceeds the
guaranteed soak limits in Table 5-5. OFF
means the profiler will not Hold during this
segment due to deviation. See
Guaranteed Soak on page 182 for details.

EDIT EVENTS

EVENT #1

.

.

.

EVENT #16

Enter the state of up to 16 discrete
outputs of this segment. These outputs
can be used to trigger any action requiring
a discrete signal, such as a relay or
another function block.

An event stays on or off for the entire
segment.

To trigger events in the middle of a
segment, you must divide the segment
into 3 segments. See Segment Events on
page 183 for details.