Honeywell VRX180 User Manual

Page 21

Advertising
background image

Introduction

Video Recorder - User Manual

7

Table 1-1 Specifications (continued)

Analog input accuracy and rated limits

Accuracy

Reference conditions

Temperature = 23°C

±

2°C (73°F

±

3°F)

Humidity = 65% RH

±

5%

Line voltage = Nominal

±

1%

Source resistance = 0 ohm
Series mode and common mode = 0 V
Frequency = Nominal

±

1%

Accuracy

Field calibration accuracy 0.05% of the selected range (IEC 873)
Factory calibration: 0.1%
Cold junction accuracy:

±

0.5°C

Rated limits and
associated drifts

Parameters

Rated limits

Influence on accuracy

Temperature

0 to 50°C (32 to 120 °F)

0.15% per 10°C of change (See
Note A)
Cold junction 0.3°C/10°C

Supply voltage

85 to 250 V

No influence

Source resistance

T/C, mV

6 µV per 400 Ohms of line
resistance max. = 1000 Ohms

RTD

0.1°C per Ohm in each wire
balanced leads
40 Ohms max. (from 0 to 400°C)

Humidity

10 to 90% RH at 25°C

0.1% max.

Long-term stability

0.1% per year


Table 1-2 Analog Input Accuracy--Linear types

Millivolts

Volts

Current

Ohms

0 to 10 mV
-10, +10 mV
0 to 20 mV
-20, 0, +20 mV
0, 50 mV
-50, 0, +50 mV
10 to 50 mV
0 to 100 mV
-100, 0, +100 mV
0 to 500 mV
-500, 0, +500 mV

0 to 1 V
-1, 0, 1 V
0 to 2 V
-2, 0, +2 V
0 to 5 V
-5, 0, +5 V
1 to 5 V
0 to 10 V
-10, 0, +10 V

0, 20 mA
4, 20 mA

0 to 200

0 to 2000

NOTE:

- The mA inputs must be connected to a 250 ohms resistor across the input terminals.